Sizing a generator for a well pump

Last updated

Well pump running and starting watts by horsepower, 120 V vs 240 V pumps, and how to find your pump's specs.

The USGS estimates that more than 43 million people in the United States get their drinking water from private wells. When the power goes out, the pump stops, and so do the toilets, the showers, and the kitchen tap. For well owners, the pump is often the load that decides how big the generator has to be.

Typical well pump wattage

Champion Power Equipment lists:

Pump Running watts Starting watts
1/2 HP well pump 750 to 1,000 1,500 to 2,000
1 HP well pump 1,000 to 2,000 2,000 to 4,000

Larger pumps (1.5 to 2 HP and up) draw more. Deep submersible pumps often have a high starting current, and that surge is the number that stalls undersized generators.

120 V or 240 V?

Many deep-well submersible pumps run on 240 volts, which matters for two reasons. First, the generator has to produce 240 V, which usually means a conventional generator of about 5,000 watts or more, or a large inverter model with 240 V output. Second, the pump is hard-wired, so it has to be connected through a transfer switch or interlock, not an extension cord.

Find your pump’s real numbers

  • Look at the pressure switch or control box (often in the basement or well house). The control box label lists horsepower, volts, and amps.
  • The size of the pump’s breaker offers a clue; a two-pole breaker means 240 V.
  • The well driller’s records usually list the pump model and horsepower.

Multiply the running amps by the volts to get running watts. If the label lists “service factor amps,” use that figure as a conservative estimate.

Sizing example

Take a 1 HP 240 V submersible (2,000 running, 4,000 starting from the chart) plus a refrigerator (400), furnace fan (800), and lights and internet (250):

  • Running total: 3,450 W
  • Largest extra surge: the well pump, 2,000 W
  • Peak: 5,450 W
  • With 20% headroom on running: about 4,300 running watts

A generator of roughly 5,000 to 7,500 running watts with 240 V output and a starting rating well above 5,450 W provides a comfortable margin. If the generator is only just large enough, start the well pump before the refrigerator and the other motors.

Save water, save fuel

The pump runs only when the pressure tank drops. Running the generator in blocks and skipping laundry during outages cuts down on pump cycles. A large pressure tank may allow several flushes and a shower between pump runs.

Try the numbers in the generator size calculator.

More on private wells

For how the pump, pressure tank, and well fit together, see our sister site Septic & Well Guide: how private wells work. If a storm also flooded the wellhead, follow after a flood: your septic system and well before drinking the water.

Why well pumps are hard to start

A submersible or jet pump is an induction motor, and induction motors draw a large inrush of current for a fraction of a second when they start. That surge can be several times the running current. A generator that easily supplies the running watts may still stall, trip its breaker, or let the voltage sag so low that the pump hums but never starts. That is why pump sizing focuses on starting watts.

Two-wire vs. three-wire submersibles

Submersible pumps come in two main types:

  • Two-wire pumps have the starting components built into the motor. There is no control box in the house, and the starting current can be high.
  • Three-wire pumps use a control box mounted in the house or well house, which holds the starting capacitor and relay. Look for the box near the pressure tank. Its label usually shows the horsepower and voltage.

Either way, the motor's horsepower, voltage, and current figures can be found on the control box, in the pump's documentation, or in the original installer's records. Some newer systems use variable-speed (constant-pressure) drives, which ramp the motor up gradually and can greatly reduce the starting surge. That makes them much easier on generators.

Larger and deep-well pumps

Exact figures depend on the motor. Deep submersible pumps often draw at or near the high end of the Champion ranges in the table above, and pumps of 1.5 hp and larger draw more. When the motor's locked-rotor amps appear in its documentation, the surge can be estimated more precisely: multiply the locked-rotor amps by the voltage.

Connecting a well pump to a generator

As covered above, a hard-wired 240-volt pump needs a generator with 240-volt output and a transfer switch or interlock installed by a licensed electrician. See our guide on transfer switches vs. interlocks.

Planning around the pressure tank

The pressure tank stores a small amount of pressurized water, often just a few usable gallons between pump cycles. During an outage, the pump can be made to start less often by:

  • filling bathtubs, pitchers, and buckets while the generator is running;
  • avoiding running the pump at the same time as other big motor loads, such as the furnace blower or AC compressor;
  • letting the pump finish its cycle before starting another large load.

If the pump runs constantly or short-cycles, check the tank's air precharge. An incorrect precharge makes the pump start more often, which is harder on both the pump and the generator.

Water for drinking and sanitation

Keep a few days of stored drinking water as a backup in case the generator fails or runs out of fuel. Ready.gov recommends storing at least one gallon of water per person per day for several days, for drinking and sanitation. After flooding, private wells may become contaminated. If the wellhead was underwater, do not drink the water until the well has been disinfected and tested.

The pressure switch starts the motor, not the faucet

A well pump does not run because you turned a tap. It runs because pressure in the tank fell to the cut-in setting on the switch. That is why a pump can start while you are in another room, and why “we’ll just not use water while the fridge is starting” is a weaker plan than it sounds. Someone filling a glass, a leaking toilet flapper, or an ice maker can drop the pressure and call for the pump at the same moment another motor starts. If the generator was sized for only one of those surges, that coincidence is the stall.

You reduce how often the switch calls for the pump by using less water and by knowing how little the pressure tank actually stores. Many tanks hold only a few gallons of usable water between cycles. A long shower can force several starts. During an outage, fill containers in one deliberate session, then leave the taps alone, so the pump runs once and rests. A larger tank, if you already have one, stretches the time between starts. It does not reduce the watts of each start. The nameplate on the motor, or the control box for a three-wire submersible, is still the wattage you type in. A 1/2-horsepower guess from a blog is how wells get paired with generators that cannot start them.

Most household submersibles are 240 volts. A generator that cannot make 240 volts cannot run them through an adapter that only changes the plug shape. The connection belongs on a transfer switch or interlock and an inlet, not on a cheater cord, and the electrician who installs it is who confirms the pump’s actual load. USGS’s page on domestic wells is background on how common private wells are, not a wiring guide. If floodwater reached the wellhead, treat the water as unsafe until it is tested, which is a different problem from whether the pump will spin. Our notes on how private wells work and wells after a flood are the place for that, not a wattage chart.

Altitude, a clogged filter, and a pump that is already failing will make a marginal generator look worse. If the pump struggles on utility power, it will not be kinder on a generator.

Free worksheet · PDF

Generator Sizing Worksheet

A printable worksheet to add up running and starting watts, pick the right size, and set up your generator safely.

  • Fill-in table for running and starting watts
  • The simple math for picking a size
  • Carbon monoxide and safe-placement checklist

Free. We email you the download link, plus an occasional plain-English guide. Unsubscribe any time. We never sell your email. Privacy

Sources

  1. Champion Power Equipment, Generator Wattage Chart
  2. USGS, Domestic (Private) Supply Wells
  3. Virginia Cooperative Extension, Estimating Appliance and Home Electronic Energy Use (BSE-301)
  4. Ready.gov, Power Outages
  5. Ready.gov, Water (emergency water storage)